DESCRIPTION
The Knauf KoolDuct® System is a pre-insulated, high performance air duct system for industrial and high-end commercial applications. The system uses a CFC-free phenolic foam board faced on both sides with reinforced foil. Patented, specially engineered, aluminum flanges are designed to connect the duct sections to assure a strong, tight closure.
APPLICATION
The Knauf KoolDuct System is used in commercial, residential and industrial applications. The ducting is versatile and can be installed internally or externally, and concealed above a false ceiling or visibly mounted. It is easily modified and repaired and can be fabricated on-site with non-powered tools.
SPECIFICATION COMPLIANCE
In U.S. and Canada:
UL (C-UL) 181, Class 1 system
DW144, Class B
SMACNA leakage, Class 6
NFPA 255
TECHNICAL DATA
Surface Burning Characteristics
• UL (C-UL) Classified
• Does not exceed 25 Flame Spread, 50 Smoke Developed when tested in accordance with ASTM E 84.
Thermal Resistance
• R-6.7 at 7/8" (1.2 R.S.I. at 22 mm)
• R-8.5 at 1 3/32" (1.5 R.S.I. at 28 mm)
Thermal Conductivity (both panels)
• 0.13 BTU in/hr2F at 75_F (0.18 W/mC at 10_C)
Service Temperature
• 176F (80C)
Maximum Air Velocity
• 5000 fpm (25 m/s)
Internal Static Pressure
• 4" w.g. (1000 Pa) Positive (UL rating: 15" w.g. positive, 4.5" w.g. negative)
Sound Attenuation
• Weighted SRI: 17dB
Microbial Growth
• Does not promote or support the growth of mold, fungi or bacteria.
NOTES
The chemical and physical properties of the Knauf KoolDuct System represent typical average values determined in accordance with accepted test methods. The data is subject to normal manufacturing variations. The data is supplied as a technical service and is subject to change without notice. References to numerical flame spread ratings are not intended to reflect hazards presented by these or any other materials under actual fire conditions. Check with your Knauf regional office to ensure information is current.